Chapter  13  Warning  CodesC2000-HS 
 
13-25
ID No.  Display on LCM Keypad  Warning Name  Description 
56 
 
Checksum error 
(PLSn) 
PLC checksum error 
Action and Reset 
Action level  PLC checksum error is detected after power on, then PLSn warning shows 
Action time  Immediately displays when the fault is detected 
Warning setting parameter  NA 
Reset method 
Check if the program is correct and re-download the program. If the fault does 
not exist, the warning automatically clears. 
Reset condition  N/A 
Record  N/A 
Cause  Corrective Actions 
The program detects checksum 
error during PLC operation 
1.  Disable PLC   
2.  Remove PLC program (Pr. 00-02=6) 
3.  Enable PLC 
4.  Re-download PLC program 
 
ID No.  Display on LCM Keypad  Warning Name  Description 
57 
 
No end command 
(PLEd) 
PLC end command is missing 
Action and Reset 
Action level 
The “End” command is missing until the last command is executed, the PLEd 
warning shows 
Action time  Immediately displays when the fault is detected 
Warning setting parameter  NA 
Reset method 
Check if the program is correct and re-download the program. If the fault does 
not exist, the warning automatically clears. 
Reset condition  N/A 
Record  N/A 
Cause  Corrective Actions 
There is no “END” command 
during PLC operation 
1.  Disable PLC   
2.  Remove PLC program (Pr. 00-02=6) 
3.  Enable PLC 
4.  Re-download PLC program