Chapter 11 Summary of Parameter SettingsC2000 Plus
11-21
03 Analog Input / Output Parameters
Pr. Parameter Name Setting Range Default
03-00 AVI Analog Input Selection 0: No function
1: Frequency command (speed limit under torque
control mode)
2: Torque command (torque limit under speed control
mode)
3: Torque compensation command
4: PID target value
5: PID feedback signal
6: Thermistor (PTC / KTY-84) input value
7: Positive torque limit
8: Negative torque limit
9: Regenerative torque limit
10: Positive / negative torque limit
11: PT100 thermistor input value
13: PID compensation value
1
03-01 ACI Analog Input Selection 0
03-02 AUI Analog Input Selection 0
03-03 AVI Analog Input Bias -100.0–100.0%
0.0
03-04 ACI Analog Input Bias -100.0–100.0% 0.0
03-05 AUI Analog Input Bias -100.0–100.0% 0.0
03-07
AVI Positive / Negative Bias
Mode
0: No bias
1: Lower than or equal to bias
2: Greater than or equal to bias
3: The absolute value of the bias voltage while serving
as the center
4: Bias serves as the center
0
03-08
ACI Positive / Negative Bias
Mode
03-09
AUI Positive / Negative Bias
Mode
03-10
Reverse Setting When Analog
Signal Input is Negative
Frequency
0: Negative frequency input is not allowed.
The digital keypad or external terminal controls the
forward and reverse direction.
1: Negative frequency is allowed.
Positive frequency = run in a forward direction;
Negative frequency = run in a reverse direction.
The digital keypad or external terminal control
cannot change the running direction.
0
03-11 AVI Analog Input Gain -500.0–500.0% 100.0
03-12 ACI Analog Input Gain -500.0–500.0% 100.0
03-13 AUI Analog Positive Input Gain -500.0–500.0% 100.0
03-14 AUI Analog Negative Input Gain -500.0–500.0% 100.0
03-15 AVI Analog Input Filter Time 0.00–20.00 sec. 0.01
03-16 ACI Analog Input Filter Time 0.00–20.00 sec. 0.01