Chapter 11 Summary of Parameter SettingsC2000 Plus
11-22
Pr. Parameter Name Setting Range Default
03-17 AUI Analog Input Filter Time 0.00–20.00 sec. 0.01
03-18 Analog Input Addition Function
0: Disabled (AVI, ACI, AUI)
1: Enabled
0
03-19
Signal Loss Selection for the
Analog Input 4–20 mA
0: Disabled
1: Continue operation at the last frequency
2: Decelerate to 0 Hz
3: Stop immediately and display ACE
4: Operate with output frequency lower limit (Pr.01-11)
and displays ANL
0
03-20 AFM1 Multi-Function Output 1
0: Output frequency (Hz)
1: Frequency command (Hz)
2: Motor speed (Hz)
3: Output current (rms)
4: Output voltage
5: DC bus voltage
6: Power factor
7: Power
8: Output torque
9: AVI
10: ACI
11: AUI
12: Iq current command
13: Iq feedback value
14: Id current command
15: Id feedback value
18: Torque command
19: PG2 frequency command
20: CANopen analog output
21: RS-485 analog output
22: Communication card analog output
23: Constant voltage output
25: CANopen and RS-485 analog output
0
03-23 AFM2 Multi-Function Output 2 0
03-21 AFM1 Analog Output Gain 1 0.0–500.0% 100.0
03-22
AFM1 Analog Output 1 in REV
Direction
0: Absolute value in output voltage
1: Reverse output 0 V; forward output 0–10 V
2: Reverse output 5–0 V; forward output 5–10 V
0
03-24 AFM2 Analog Output Gain 2 0.0–500.0% 100.0