Chapter 12 Description of Parameter SettingsCP2000
12.1-06-19
Status 4: The drive is in STOP; Pr.06-48≠0 ; Pr.07-02=0
When the drive starts, it executes Pr.06-48 as the DC brake. The DC brake current level is 20
times the Pr.06-47 setting value. In this period, if an OPHL happens within the time for Pr.06-48,
the drive executes the Pr.06-45 setting after the drive starts counting for half the time of
Pr.06-48.
Status 4-1: Pr.06-48 ≠ 0, Pr.07-02 = 0 (No OPHL detected before operation)
Status 4-2: Pr.06-48 ≠ 0, Pr.07-02 = 0 (OPHL detected before operation)
LvX Auto-Reset
Default: 0
Settings 0: Disable
1: Enable
Time for Input Phase Loss Detection
Default: 0.20
Settings 0.00–600.00 sec.
Sets the time for input phase loss detection; setting 0.20 seconds means to check every 0.20 sec.