Chapter 15 CANopen OverviewCP2000
15-20
15-5 CANopen Fault Codes
* Refer to setting value of Pr.06-17–Pr.06-22.
ID
No.*
Display Fault code
Description
CANopen
fault register
(bit0–7)
CANopen
fault code
1
0001H
Over-current during acceleration
1 2213 H
2
0002H
Over-current during deceleration
1 2213 H
3
0003H
Over-current during steady status
operation
1 2214H
4
0004H
Ground fault. When one of the output
terminals is grounded, the short
circuit current is more than 50% of
AC motor drive rated current.
NOTE: The short circuit protection is provided
for the AC motor drive protection, not to
protect the user.
1 2240H
5
0005H
Short-circuit is detected between
upper bridge and lower bridge of the
IGBT module.
1 2250H
6
0006H
Over-current at stop. Hardware
failure in current detection
1 2314H
7
0007H
Over-voltage during acceleration.
Hardware failure in current detection
2 3210H
8
0008H
Over-voltage during deceleration.
Hardware failure in current detection.
2 3210H

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD150CP43B-21 and is the answer not in the manual?

Delta VFD150CP43B-21 Specifications

General IconGeneral
Output Phase3-phase
Braking UnitBuilt-in
ProtectionIP20
Cooling MethodForced air cooling
Output Voltage460 VAC, 3-phase
Control MethodV/F Control, Sensorless Vector Control
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overload, Overheat, Short Circuit
Communication InterfaceRS-485, Modbus RTU
Operating Temperature-10°C to 50°C
Storage Temperature-20 ~ 60°C
Altitude1000m

Related product manuals