Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-08-13
3) PID Feedback Value Rate Percentage (PID is in use, Pr.08-00 ≠ 0 and Pr.08-18 = 1) 
When the PID feedback value reaches the sleep level percentage, the drive starts to count 
the sleep time and the output frequency starts to decrease. If the drive exceeds the preset sleep 
time, then the drive is in sleep mode (0 Hz). If the drive does not reach the preset sleep time, it 
remains at the lower frequency limit (if there is a preset of lower limit.), or it remains at the 
minimum output frequency set for Pr.01-07 and waits until it reaches the sleep time before going 
into sleep mode (0 Hz). 
When the PID feedback value reaches the wake-up percentage, the drive starts to count the 
wake-up delay time. Once it reaches the wake-up delay time, the drive starts to catch up to reach 
the PID Frequency command value by the acceleration time. 
Example 01: PID negative feedback 
  Pr.08-10 must > Pr.08-11 
  30kg is the reference 
  Set the parameter: 
Pr.03-00 = 5 (AVI is PID feedback) 
Pr.08-00 = 1 (PID
 negative feedback: AVI 
simulation input function select) 
Pr.08-10 = 40% (Sleep reference:   
12kg = 40%*30kg) 
Pr.08-11 = 20% (Wake-up reference:   
6kg = 20%*30kg) 
Case 01: If feedback >12kg, frequency decreases. 
Case 02: If feedback <6kg, frequency increases. 
 
Area 
PID  
Physical quantity 
Sleep area 
> 12 kg, the drive 
goes into sleep, the 
motor goes into sleep 
Excessive 
area 
between 6 kg and 12 
kg, the drive remains 
in current state 
Wake-up area 
< 6 kg, the drive 
wakes-up, the motor 
wakes-up