Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-11-6
 
 
11-13 
PDFF Gain Value 
 
 
   
 Default: 30 
 
 
Settings 0–200% 
  This parameter is invalid when Pr.05-24 = 1. 
  This parameter is valid only when Pr.11-00 bit0 = 1. 
  After you estimate and set Pr.11-00 bit0=1 (auto-tuning), use Pr.11-13 to reduce overshoot. 
However, a shift of the curve may occur earlier. In this case, you can set Pr.11-13 = 0 first, and 
then increase the setting value to "a condition with best acceleration and without overshoot" 
when the acceleration time meets your application but overshoot occurs.   
  Increasing Pr.11-13 improves the overshoot of speed tracking, but an excessive value may 
reduce the transient response. 
  Increasing Pr.11-13 enhances the system stiffness in high-speed steady state, and reduce the 
speed transient fluctuation at a sudden loading. 
  Ensure that you set Pr.11-01 system inertia correctly to get excellent improvement of the speed 
response. 
 
 
11-14 
ASR Output Low Pass Filter Time 
 
 
   
 Default: 0.004 
 
 
Settings 0.000–0.350 sec. 
  Set the ASR command filter time.