Chapter 12 Description of Parameter SettingsC2000 Plus 
 
 
12.2-36 
  No-load / light-load operation adjustment 
8.  Start the motor with no-load 
(a) Set Pr.11-00 = 1 Auto-tuning for ASR and APR 
(b) Start the motor without load, and operates the motor to 1/2 of rated rotor speed 
a. If the start direction is wrong, starting rotation is not smooth (ocA) or the motor salient ratio 
(Lq / Ld) is low, increase Pr. 10-52 (injection magnitude) and Pr. 10-42 (initial angel detection 
pulse value) to improve the accuracy of the angle detection. 
b. If Pr. 10-51 (injection frequency) is close to the rated motor frequency (Pr. 01-01), then 
increase Pr.10-51 to avoid the angle detection difference caused by motor rated frequency.   
9.  Acceleration test with no load / light load 
A1. Accelerate to rated frequency and observe if the motor operates stably. 
a. If the motor output rotor speed presents periodic low-frequency wave, increase Pr. 11-04 
(ASR2 high-speed bandwidth), or increase Pr. 10-32 (PM FOC sensorless speed 
estimator bandwidth). 
b. If the output frequency reflects high-frequency vibration, decrease Pr.11-04 or decrease 
Pr.10-32. 
A2. Accelerate the motor to the maximum frequency, and observe if it operates stably. 
If the motor stalls when accelerating to the maximum rotor speed, increase Pr.10-32 (PM 
FOC sensoress speed estimator bandwidth) and Pr.10-34 (PM sensorless speed 
estimator low-pass filter gain). 
Setting curve for speed regulator (ASR) and related parameters: 
 
 
 
 
Parameter  Description  Default 
Pr.11-00 System control  0 
Pr.11-01  Per unit of system inertia  256 
Pr.11-02 
ASR1 / ASR2 switch frequency 
(it is suggested to set the switch 
frequency higher than Pr.10-39) 
7 Hz 
Pr.11-03  ASR1 low-speed bandwidth  10 Hz 
Pr.11-04  ASR2 high-speed bandwidth  10 Hz 
Pr.11-05  Zero-speed bandwidth  10 Hz