Chapter 12 Description of Parameter SettingsC2000 Plus 
 
 
12.2-37
III. IPM Sensorless adjustment flowchart for operation starts with load 
 
 
 
 
 
Low-frequency 
loaded performance 
normal?
Increase ASR1 bandwidth 
Pr.11-03
Increase system inertia 
Pr.11-01
Increase speed estimation bandwidth 
Pr.10-32
Low-frequency cannot start with 
load or rotates not well
Decrease ASR1 bandwidth 
Pr.11-03
Decrease system inertia 
Pr.11-01
Decrease speed estimation bandwidth 
Pr.10-32
Low-frequency over 
current causes wave or oc
Accelerated rated 
frequency is normal?
Cannot follow the accel. time, 
the response is too slow
NO
NO
YES
Constant speed 
operation normal?
Increase speed estimation 
bandwidth Pr.10-32
Increase low-pass filter gain 
Pr.10-34
Cyclicity low-frequency wave 
of motor frequency
Decrease speed estimation 
bandwidth Pr.10-32
Decrease low-pass filter gain 
Pr.10-34
Strong high-frequency 
vibration of motor frequency
NO
YES
YES
Finish
Increase ASR2 bandwidth 
Pr.11-04
Increase ASR1 bandwidth 
Pr.11-03
Decrease ASR2 bandwidth 
Pr.11-04
Decrease ASR1 bandwidth 
Pr.11-03
Over-acceleration causes 
vibration or ocA
10. Running Test 
with Load
B1. Low-frequency loaded 
performance
(Frequency of Pr.10-39 and below)
B2. Loaded acceleration 
performance test
11. Steady State Test at 
Constant Speed Run