Chapter 12 Descriptions of Parameter SettingsMS300
451
14 Protection Parameters (2)
You can set this parameter during operation.
14-50
Output Frequency at Malfunction 2
14-54
Output Frequency at Malfunction 3
14-58
Output Frequency at Malfunction 4
14-62
Output Frequency at Malfunction 5
14-66
Output Frequency at Malfunction 6
Default: Read only
Settings
0.00–599.00 Hz
When an error occurs, you can check the output frequency for the malfunction. If the error
happens again, this parameter overwrites the previous record.
14-51
DC bus Voltage at Malfunction 2
14-55
DC bus Voltage at Malfunction 3
14-59
DC bus Voltage at Malfunction 4
14-63
DC bus Voltage at Malfunction 5
14-67
DC bus Voltage at Malfunction 6
Default: Read only
Settings
0.06553.5 V
When an error occurs, you can check the DC bus voltage for the malfunction. If the error
happens again, this parameter overwrites the previous record.
14-52
Output Current at Malfunction 2
14-56
Output Current at Malfunction 3
14-60
Output Current at Malfunction 4
14-64
Output Current at Malfunction 5
14-68
Output Current at Malfunction 6
Default: Read only
Settings
0.00–655.35 Amps
When an error occurs, you can check the output current for the malfunction. If the error happens
again, this parameter overwrites the previous record.
14-53
IGBT Temperature at Malfunction 2
14-57
IGBT Temperature at Malfunction 3
14-61
IGBT Temperature at Malfunction 4
14-65
IGBT Temperature at Malfunction 5
14-69
IGBT Temperature at Malfunction 6
Default: Read only
Settings
-3276.73276.7
o
C
When an error occurs, you can check the IGBT temperature for the malfunction. If the error
happens again, this parameter overwrites the previous record.

Table of Contents

Other manuals for Delta VFD17AMS43ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD17AMS43ANSAA and is the answer not in the manual?

Delta VFD17AMS43ANSAA Specifications

General IconGeneral
Input Phase3-Phase
Rated Output Current17 A
Protection LevelIP20
Control MethodV/F control, Sensorless Vector Control (SVC)
Protection FeaturesOvervoltage, Overcurrent, Overload, Overtemperature, Short Circuit
Cooling MethodFan Cooled
Communication InterfaceRS-485
Operating Temperature-10°C to 50°C
Storage Temperature-20°C to 60°C
Altitude1000m