Chapter 11 Summary of Parameter SettingsMS300
209
65: Accumulated motor operation record (day) (r.)
(refer to Pr.05-32)
Coefficient Gain in Actual
Output Frequency
Parameter Protection
Password Input
0–65535
0–4: the number of password attempts allowed
Parameter Protection
Password Setting
0–65535
0: No password protection or password entered correctly
(Pr.00-07)
1: Parameter has been set
0: Speed Control mode
2: Torque mode
0: IMVF (IM V/F control)
1: IMVFPG (IM V/F control + MI7 one-phase pulse input)
2: IM/PM SVC (IM / PM space vector control)
5: IMFOC Sensorless
(IM field-oriented sensorless vector control)
0: Normal load
1: Heavy load
Normal load: 2–15 kHz
Heavy load: 2–15 kHz
NOTE: When Pr.00-11 = 5 (IMFOC Sensorless), the maximum
setting value for the carrier frequency is 10 kHz.
bit 0: Control command is forced by PLC control
bit 1: Frequency command is forced by PLC control
bit 3: Torque command is forced by PLC control
Master Frequency
Command Source
(AUTO, REMOTE)
0: Digital keypad
1: RS-485 communication input
2: External analog input (Refer to Pr.03-00)
3: External UP / DOWN terminal
(multi-function input terminals)
4: Pulse input without direction command
(refer to Pr.10-16 without considering direction)
6: CANopen communication card
7: Digital keypad potentiometer knob
8: Communication card (does not include CANopen card)
9: PID controller
NOTE:
HOA (Hand-Off-Auto) function is valid only when you use with
MO function setting 42 and 56 or with KPC-CC01 (optional).