2-12
Terminal  Features  Factory Setting (NPN Mode) 
SON  Run-Stop  Terminal SON-COM: ON for Running; OFF for Stop 
EMG  External error input  External error input 
RES  Reset from error  Reset from error 
MI3  Multi-function input selection 3 
MI4  Multi-function input selection 4 
MI5  Multi-function input selection 5 
Configured as no function in factory 
When it is ON, the input voltage is 24Vdc (Max:30Vdc) 
and then input impedance is 3.75k; when it is OFF, the 
tolerable leakage current is 10A. 
COM 
Common ground (Sink) for digital 
control signals   
Common ground for multi-function input terminals 
+E24V 
Common source for digital 
control signals   
+24V 80mA 
DCM 
Common ground (Sink) for digital 
control signals   
Common ground for multi-function input terminals 
RA  Error terminal 1 (Relay N.O. a) 
RB  Error terminal 1 (Relay N.C. b) 
RC 
Command contact for 
multi-function output terminals 
(Relay) 
Resistive load 
5A(N.O.)/3A(N.C.) 240VAC 
5A(N.O.)/3A(N.C.) 24VDC 
Inductive load 
1.5A(N.O.)/0.5A(N.C.) 240VAC 
1.5A(N.O.)/0.5A(N.C.) 24VDC 
MO1 
Multi-function output terminal 1 
(photocoupler) 
MO2 
Multi-function output terminal 2 
(photocoupler) 
The Hybrid servo drive sends various monitoring 
signals by means of open-collector configuration.   
MO1
~
MO2
internal circuit
 
MCM
Max: 48Vdc/50mA
 
MCM 
Common ground for 
Multi-function output terminal 
(photocoupler) 
Max 48Vdc 50mA 
PO 
Pressure feedback 
Impedance: 200k  Resolution: 12 bits 
Range: 0 – 10V = 0 – the maximum pressure feedback 
value (Parameter 00-08)   
PI 
Pressure Command 
Impedance: 200k  Resolution: 12 bits 
Range: 0 – 10V = 0 – the maximum pressure command 
value (Parameter 00-07)   
QI 
 
ACM
PO/PI/QI
internal circuit
 
PO/PI/QI circuit
 
Flow rate command 
Impedance: 200k  Resolution: 12 bits 
Range: 0 – 10V = 0 – the maximum flow rate 
AUI  Analog Voltage  Impedance: 11.3k