Chapter 11 Summary of Parameter SettingsMS300
238
Pr.
Explanation
Settings
Default
06-53
Input Phase Loss
Detection Action (Orp)
0: Fault and ramp to stop
1: Fault and coast to stop
0
06-55
Derating Protection
0: Constant rated current and limit carrier frequency by
load current and temperature
1: Constant carrier frequency and limit load current by
setting carrier frequency
2: Constant rated current (same as setting 0), but close
current limit
0
06-56
PT100 Voltage Level 1
0.000–10.000 V
5.000
06-57
PT100 Voltage Level 2
0.000–10.000 V
7.000
06-58
PT100 Level 1 Frequency
Protection
0.00–599.00 Hz
0.00
06-59
PT100 Activation Level 1
Protection Frequency
Delay Time
0–6000 sec.
60
06-60
Software Detection GFF
Current Level
0.0–6553.5%
60.0
06-61
Software Detection GFF
Filter Time
0.00–655.35 sec.
0.10
06-63
Operation Time of Fault
Record 1 (Days)
0–65535 days
Read only
06-64
Operation Time of Fault
Record 1 (Minutes)
0–1439 min.
Read only
06-65
Operation Time of Fault
Record 2 (Days)
0–65535 days
Read only
06-66
Operation Time of Fault
Record 2 (Minutes)
0–1439 min.
Read only
06-67
Operation Time of Fault
Record 3 (Days)
0–65535 days
Read only
06-68
Operation Time of Fault
Record 3 (Minutes)
0–1439 min.
Read only
06-69
Operation Time of Fault
Record 4 (Days)
0–65535 days
Read only
06-70
Operation Time of Fault
Record 4 (Minutes)
0–1439 min.
Read only
06-71
Low Current Setting Level
0.0–100.0%
0.0
06-72
Low Current Detection
Time
0.00–360.00 sec.
0.00