Chapter 11 Summary of Parameter SettingsMS300
237
Pr.
Explanation
Settings
Default
06-30
PTC Level
0.0–100.0%
50.0
06-31
Frequency Command at
Malfunction
0.00–599.00 Hz
Read only
06-32
Output Frequency at
Malfunction
0.00–599.00 Hz
Read only
06-33
Output Voltage at
Malfunction
0.0–6553.5 V
Read only
06-34
DC bus Voltage at
Malfunction
0.0–6553.5 V
Read only
06-35
Output Current at
Malfunction
0.00–655.35 Amp
Read only
06-36
IGBT Temperature at
Malfunction
-3276.7–3276.7
o
C
Read only
06-38
Motor Speed at
Malfunction
-32767–32767 rpm
Read only
06-39
Torque Command at
Malfunction
-32767–32767%
Read only
06-40
Status of the Multi-
Function Input Terminal at
Malfunction
0000h–FFFFh
Read only
06-41
Status of the Multi-
Function Output Terminal
at Malfunction
0000h–FFFFh
Read only
06-42
Drive Status at
Malfunction
0000h–FFFFh
Read only
06-44
STO Latch Selection
0: STO latch
1: STO no latch
0
06-45
Output Phase Loss
Detection Action (OPHL)
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: No warning
3
06-46
Detection Time for Output
Phase Loss
0.000–65.535 sec.
0.500
06-47
Current Detection Level
for Output Phase Loss
0.00–100.00%
1.00
06-48
DC Brake Time for Output
Phase Loss
0.000–65.535 sec.
0.000
06-49
Lvx Auto-Reset
0: Disable
1: Enable
0