Chapter 12 Descriptions of Parameter SettingsMS300
310
External interrupt B.B.
input (Base Block)
Activates when external interrupt (B.B.) stop output occurs in the
drive.
Activates when a warning is detected.
Activates when over-voltage is detected.
Over-current stall
prevention
Activates when the over-current stall prevention is detected.
Over-voltage stall
prevention
Activates when over-voltage stall prevention is detected.
Activates when the source of operation command is not
controlled by the digital keypad (Pr.00-21 ≠ 0).
Activates when the operation direction is forward.
Activates when the operation direction is reverse.
Output when frequency
≥ Pr.02-34
Activates when frequency is ≥ Pr.02-34
(actual output H ≥ Pr.02-34).
Output when frequency
< Pr.02-34
Activates when frequency is < Pr.02-34
(actual output H < Pr.02-34).
Y-connection for the
motor coil
Activates when Pr.05-24 = 1, the frequency output is lower than
Pr.05-23 minus 2 Hz and the time is longer than Pr.05-25.
∆-connection for the
motor coil
Activates when Pr.05-24 = 1, the frequency output is higher than
Pr.05-23 plus 2 Hz and the time is longer than Pr.05-25.
Zero speed
(actual output frequency)
Activates when the actual output frequency is 0
(the drive is in RUN mode).
Zero speed including
stop
(actual output frequency)
Activates when the actual output frequency is 0 or stopped.
Error output selection 1
(Pr.06-23)
Activates when Pr.06-23 is ON.
Error output selection 2
(Pr.06-24)
Activates when Pr.06-24 is ON.
Error output selection 3
(Pr.06-25)
Activates when Pr.06-25 is ON.
Error output selection 4
(Pr.06-26)
Activates when Pr.06-26 is ON.
Speed reached
(including Stop)
Activates when the drive’s output frequency reaches the setting
frequency or stopped.
Use this function with Pr.02-34 and Pr.02-58.
Refer to Pr.02-34 and 02-58 for details and application examples.
Actual motor speed
detection
Activates when the motor actual speed is less than Pr.02-47.
Use this function with Pr.06-71–Pr.06-73.