EasyManuals Logo

Delta VFD2A8MS21ANSAA User Manual

Delta VFD2A8MS21ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #369 background imageLoading...
Page #369 background image
Chapter 12 Descriptions of Parameter SettingsMS300
360
06-06
Over-Torque Detection Selection (Motor 1)
Default: 0
Settings
0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
06-09
Over-Torque Detection Selection (Motor 2)
Default: 0
Settings
0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
When you set Pr.06-06 and Pr.06-09 to 1 or 3, a warning message displays but there is no error
record.
When you set Pr.06-06 and Pr.06-09 to 2 or 4, an error message displays and there is an error
record.
06-07
Over-Torque Detection Level (Motor 1)
Default: 120
Settings
10250% (100% corresponds to the rated current of the drive)
06-08
Over-Torque Detection Time (Motor 1)
Default: 0.1
Settings
0.160.0 sec.
06-10
Over-Torque Detection Level (Motor 2)
Default: 120
Settings
10–250% (100% corresponds to the rated current of the drive)
06-11
Over-Torque Detection Time (Motor 2)
Default: 0.1
Settings
0.160.0 sec.
When the output current exceeds the over-torque detection level (Pr.06-07 or Pr.06-10) and also
exceeds the over-torque detection time (Pr.06-08 or Pr.06-11), the over-torque detection follows
the setting of Pr.06-06 and Pr.06-09.
When you set Pr.06-06 or Pr.06-09 to 1 or 3, an ot1 / ot2 warning displays while the drive keeps
running after over-torque detection. The warning remains on until the output current is smaller
than 5% of the over-torque detection level.

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A8MS21ANSAA and is the answer not in the manual?

Delta VFD2A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals