Chapter 12 Descriptions of Parameter SettingsMS300
361
When you set Pr.06-06 or Pr.06-09 to 2 or 4, an ot1 / ot2 warning displays and the drive stops
running after over-torque detection. The drive does not run until you manually reset it.
06-12
Current Limit
Default: 150
Settings
0–250% (100% corresponds to the rated current of the drive)
Set the maximum output current of the drive. Use Pr.11-1711-20 to set the drive’s output
current limit.
06-13
Electronic Thermal Relay Selection 1 (Motor 1)
06-27
Electronic Thermal Relay Selection 2 (Motor 2)
Default: 2
Settings
0: Inverter motor (with external forced cooling)
1: Standard motor (motor with fan on the shaft)
2: Disable
Prevents self-cooled motor from overheating under low speed. Use an electronic thermal relay to
limit the drive’s output power.
Setting the parameter to 0 is suitable for an inverter motor (motor fan using an independent
power supply). For this kind of motor, there is no significant correlation between cooling capacity
and motor speed. Therefore, the action of electronic thermal relays remains stable in low speed
to ensure the load capability of the motor in low speed.

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A8MS21ANSAA and is the answer not in the manual?

Delta VFD2A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals