EasyManuals Logo

Delta VFD2A8MS21ANSAA User Manual

Delta VFD2A8MS21ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #444 background imageLoading...
Page #444 background image
Chapter 12 Descriptions of Parameter SettingsMS300
435
All control modes are based on 100% of the motor rated current except:
IM: VF, VFPG, SVC
PM: PMSVC
11-21
Flux Weakening Curve for Motor 1 Gain Value
Default: 90
Settings
0–200%
11-22
Flux Weakening Curve for Motor 2 Gain Value
Default: 90
Settings
0–200%
Adjusts the output voltage for the flux weakening curve.
For the spindle application, use this adjustment method:
1. Run the motor to the highest frequency.
2. Observe the output voltage.
3. Adjust the Pr.11-21 (motor 1) or Pr.11-22 (motor 2) setting to make the output voltage reach
the motor rated voltage.
4. The larger the setting value, the greater the output voltage.

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A8MS21ANSAA and is the answer not in the manual?

Delta VFD2A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals