Chapter 13 Warning CodesMS300
502
ID No.
Display on LCD Keypad
Warning Name
Description
41
CANopen station
address error (CAdn)
CANopen station address error (only supports 1–127)
Action and Reset
Action Condition
CANopen station address error
Action Time
Immediately act when the fault is detected
Warning Setting Parameter
N/A
Reset Method
Manual Reset
Reset Condition
Pr.00-02 = 7
Record
When Pr.00-21 ≠ 3, CAdn is a “Warning”, and the warning is not recorded.
Cause
Corrective Actions
Incorrect setting of CANopen
station address
1. Disable CANopen (Pr.09-36 = 0)
2. Reset CANopen (Pr.00-02 = 7)
3. Reset CANopen station address (Pr.09-36)