EasyManuals Logo

Delta VFD2A8MS21ANSAA User Manual

Delta VFD2A8MS21ANSAA
805 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #512 background imageLoading...
Page #512 background image
Chapter 13 Warning CodesMS300
503
ID No.
Display on LCD Keypad
Warning Name
Description
42
CANopen memory
error (CFrn)
CANopen memory error
Action and Reset
Action Condition
When you update the firmware version of the control board, the FRAM internal
data does not change, then CFrn warning occurs.
Action Time
Immediately act when the fault is detected
Warning Setting Parameter
N/A
Reset Method
Manual Reset
Reset Condition
Pr.00-02 = 7
Record
When Pr.00-21 ≠ 3, CFrn is a “Warning”, and the warning is not recorded.
Cause
Corrective Actions
CANopen internal memory error
1. Disable CANopen (Pr.09-36 = 0)
2. Reset CANopen (Pr.00-20 = 7)
3. Reset CANopen station address (Pr.09-36)

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A8MS21ANSAA and is the answer not in the manual?

Delta VFD2A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals