Chapter 14 Fault CodesMS300
583
ID
Display on LCD Keypad
Fault Name
Fault Descriptions
44
PG feedback stall
(PGF3)
Under PG mode, when the motor frequency exceeds
the encoder observer stall level (Pr.10-10) and starts to
count, the fault time is longer than the detection time of
encoder observer stall (Pr.10-11), then PGF3 fault
occurs.
Action and Reset
Action Condition
Pr.10-10
Action Time
Pr.10-11
Fault Treatment Parameter
Pr.10-12
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
Reset Method
Manual reset
Reset Condition
Immediately reset
Record
Yes
Cause
Corrective Actions
Incorrect setting of encoder
parameter
Reset encoder parameter (Pr.10-01)
Pr. 01-00 is set too small
Set proper value for Pr.01-00.
Incorrect setting for ASR
parameters and accel./decel. time
Reset ASR parameters.
Set correct accel./decel. time.
Incorrect setting for PG feedback
stall
Reset proper values for Pr.10-10 and Pr.10-11

Table of Contents

Other manuals for Delta VFD2A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD2A8MS21ANSAA and is the answer not in the manual?

Delta VFD2A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD2A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals