Chapter 14 Fault CodesMS300
585
Analog input loss (including all the 4–20 mA analog
signal)
When the analog input is < 4 mA (only detects 4–20 mA analog input)
Fault Treatment Parameter
Pr.03-19
0: Disable
1: Continue operation at the last frequency
(warning, ANL is displayed on the keypad)
2: Decelerate to stop (warning, ANL is displayed on the keypad)
3: Stop immediately and display ACE
When Pr.03-19 = 1 or 2, ACE is a “Warning”. When analog input
signal is > 4 mA, the warning is automatically cleared.
When Pr.03-19 = 3, ACE is a “Fault”. You must reset manually.
When Pr.03-19 = 3, ACE is a “Fault”, and the fault is recorded.
ACI cable is loose or cut off
Tighten the terminal.
Replace the cable with a new one.
Replace the device with a new one.
Check all the wiring. If ACE still exists, return to the factory for repair.