Page #623 background image
Chapter 14 Fault CodesMS300
614
ID
Display on LCD Keypad
Fault Name
Fault Descriptions
106
CANopen station
address error
(CAdE)
CANopen station address error (only supports 1–127)
Action and Reset
Action Condition
Software detection
Action Time
Immediately act
Fault Treatment Parameter
N/A
Reset Method
Manual reset (Pr.00-02 = 7)
Reset Condition
N/A
Record
Yes
Cause
Corrective Actions
Incorrect setting of CANopen
station address
1. Disable CANopen (Pr.09-36 = 0)
2. Reset CANopen (Pr.00-02 = 7)
3. Reset CANopen station address (Pr.09-36)