Chapter 11 Summary of Parameter SettingsC2000-HS
11-19
Pr. Parameter Name Setting Range Default
03-59 ACI mid-point
Pr. 03-29=0, 0.00–20.00mA
Pr. 03-29=1, 0.00–10.00V
Pr. 03-29=2, 0.00–20.00mA
12.00
5.00
10.00
03-60 ACI proportional mid-point -100.00–100.00% 50.00
03-61 ACI highest point
Pr. 03-29=0, 0.00–20.00mA
Pr. 03-29=1, 0.00–10.00V
Pr. 03-29=2, 0.00–20.00mA
20.00
10.00
20.00
03-62 ACI proportional highest point -100.00–100.00% 100.00
03-63 Positive AUI voltage lowest point 0.00–10.00V 0.00
03-64
Positive AUI voltage proportional
lowest point
-100.00%–100.00% 0.00
03-65 Positive AUI voltage mid-point 0.00–10.00V 5.00
03-66
Positive AUI voltage proportional
mid-point
-100.00%–100.00% 50.00
03-67
Positive AUI voltage highest
point
0.00–10.00V 10.00
03-68
Positive AUI voltage proportional
highest point
-100.00%–100.00% 100.00
03-69
Negative AUI voltage highest
point
-10.00V–0.00V 0.00
03-70
Negative AUI voltage
proportional highest point
-100.00%–100.00% 0.00
03-71 Negative AUI voltage mid-point -10.00–0.00V -5.00
03-72
Negative AUI voltage
proportional mid-point
-100.00%–100.00% -50.00
03-73
Negative AUI voltage lowest
point
-10.00–0.00V -10.00
03-74
Negative AUI voltage
proportional lowest point
-100.00%–100.00% -100.00