Chapter 12 Description of Parameter SettingsC2000-HS
12.1-01-2
Mid-point Voltage 1 of Motor 1
Default: 22.0
Settings 0.0–480.0 V
Mid-point Frequency 1 of Motor 2
Default: 3.0
Settings 0.0–1500.0 Hz
The upper limit of setting range is the same as Pr. 01-00 maximum operation frequency.
Mid-point Voltage 1 of Motor 2
Default: 22.0
Settings 0.0–480.0 V
Mid-point Frequency 2 of Motor 1
Default: 1.5
Settings 0.0–1500.0 Hz
The upper limit of setting range is the same as Pr. 01-00 maximum operation frequency.
Mid-point Voltage 2 of Motor 1
Default: 10.0
Settings 0.0–480.0 V
Mid-point Frequency 2 of Motor 2
Default: 1.5
Settings 0.0–1500.0 Hz
The upper limit of setting range is the same as Pr. 01-00 maximum operation frequency.
Mid-point Voltage 2 of Motor 2
Default: 10.0
Settings 0.0–480.0 V
Minimum Output Frequency of Motor 1
Default: 0.5
Settings 0.0–1500.0 Hz
The upper limit of setting range is the same as Pr. 01-00 maximum operation frequency.
Minimum Output Voltage of Motor 1
Default: 2.0
Settings 0.0–480.0 V
Minimum Output Frequency of Motor 2
Default: 0.5
Settings 0.0–1500.0 Hz
The upper limit of setting range is the same as Pr. 01-00 maximum operation frequency.