Chapter 12 Description of Parameter SettingsC2000-HS
12.1-02-28
When the drive outputs current higher than the setting for Pr. 02-33 Pivot Point of the Current (≥
Pr. 02-33), and outputs frequency higher than the setting for Pr. 02-34 Pivot Point of the
Frequency (≥ Pr. 02-34), multi-function output Pr. 02-13, Pr. 02-14, Pr. 02-16 and Pr. 02-17 are
set to 42 after the delay time setting for Pr. 02-32.
When the Pivot Point of the Current 's setting Pr. 02-57≠0 and when the output current of the
drive is lower than the setting for Pr. 02-57 (< Pr. 02-57), or the output frequency is lower than
the setting for Pr.02-58 (< Pr. 02-58), disable the setting #42 of the multi-function output Pr.
02-13, Pr. 02-14, Pr. 02-16 and Pr. 02-17.
When Pr. 02-57 = 0, the output current is lower than the setting for Pr. 02-33 Pivot Point of the
current (< Pr. 02-33), or the output frequency is lower than the setting for Pr. 02-58(< Pr. 02-58),
disable the setting of #42 of the multi-function output Pr. 02-13, Pr. 02-14, Pr. 02-16 and Pr.
02-17.
When using crane application, and MOx=42, Pr. 02-34 must be larger than Pr. 02-58; and Pr.
02-33 must be larger than Pr. 02-57.
Frequency Reached Detection Amplitude
Default: 0.0
Settings 0.0–1500.0 Hz
The upper limit of setting range is the same as the maximum operating frequency for Pr. 01-00.
IO Card Types
Default: Read only
Settings Read only
1: EMC-BPS01
4: EMC-D611A
5: EMC-D42A
6: EMC-R6AA
11: EMC-A22A
DFM Output Selection
Default: 0
Settings 0: Use frequency with speed control as DFM output frequency
1: Use frequency with system acceleration / deceleration as DFM output
frequency
Internal / External Multi-function Input Terminal Selection
Default: 0000h
Settings 0000–FFFFh
Selects the terminals MI1–MI15 to be internal terminals or external terminals. When the MIx is set
as internal terminal, the corresponding external terminal function is disabled.
To activate internal terminals via Pr. 02-75 setting.