Chapter 11 Summary of Parameter SettingsC2000-HS
11-15
Pr. Parameter Name Setting Range Default
02-35
External operation control selection
after reset and activate
0: Disable
1: Drive runs if the RUN command remains after
reset or reboot
0
02-47 Motor zero-speed level 0–65535 rpm 0
02-48
Maximum frequency of resolution
switch
0.0–1500.0 Hz
600.0
02-49
Switch delay time of maximum output
frequency
0.000–65.000 sec. 0.000
02-50
Display the status of multi-function
input terminal
Monitor the status of multi-function input terminals
Read
only
02-51
Display the status of multi-function
output terminal
Monitor the status of multi-function output
terminals
Read
only
02-52
Display the external multi-function
input terminals used by PLC
Monitor the status of PLC input terminals
Read
only
02-53
Display the external multi-function
output terminals used by PLC
Monitor the status of PLC output terminals
Read
only
02-54
Display the frequency command
executed by external terminal
0.0–1500.0 Hz (Read only)
Read
only
02-56 Brake release check time 0.000–65.000 sec. 0.000
02-57
Multi-function output terminal:
function 42: brake current check
point
0–100% 0
02-58
Multi-function output terminal
(function 42): brake frequency check
point
0.0–1500.0 Hz 0.0
02-63
Frequency reached detection
amplitude
0.0–1500.0 Hz 0.0
02-70 IO card types
1: EMC-BPS01
4: EMC-D611A
5: EMC-D42A
6: EMC-R6AA
11: EMC-A22A
Read
only
02-71 DFM output selection
0: Use frequency with speed control as DFM
output frequency
1: Use frequency with system acceleration /
deceleration as DFM output frequency
0
02-74
Internal / external multi-function input
terminal selection
0000–FFFFh 0000h
02-75
Internal multi-function output terminal
selection
0000–FFFFh 0000h