Chapter 11 Summary of Parameter SettingsC2000-HS
11-36
Pr. Parameter Name Setting Range Default
08-18 Sleep mode function setting
0: Refer to PID output command
1: Refer to PID feedback signal
0
08-19 Wake-up integral limit 0.0–200.0% 50.0
08-20 PID mode selection
0: Serial connection
1: Parallel connection
0
08-21
Enable PID to change the
operation direction
0: Operation direction cannot be changed
1: Operation direction can be changed
0
08-22 Wake-up delay time 0.00–600.00 sec. 0.00
08-23 PID control flag
bit0 = 1, PID running in reverse follows the setting for
Pr. 00-23.
bit0 = 0, PID running in reverse follows PID’s calculated
value.
bit1 = 1, second decimal place of PID Kp
bit1 = 0, first decimal place of PID Kp
0000h
08-26
PID output command limit
(reverse limit)
0.0–100.0% 100.0
08-27
Acceleration / deceleration time
for PID command
0.00–655.35 sec. 0.00
08-28 PID error width 0.00–100.00% 0.06