EasyManuals Logo

Delta VFD370CP43B-21 User Manual

Delta VFD370CP43B-21
868 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #381 background imageLoading...
Page #381 background image
Chapter 12 Description of Parameter SettingsCP2000
12.1-01-5
Start-Up Frequency
Default: 0.50
Settings 0.00–599.00 Hz
When the starting frequency is higher than the minimum output frequency, the drives’ output is
from the starting frequency to the setting frequency. Refer to the following diagram for details.
Fcmd: frequency command
Fstart: start-up frequency (Pr.01-09)
fstart: actual start-up frequency of drive
Fmin: 4th output frequency setting (Pr.01-07 / Pr.01-41)
Flow: output frequency lower limit (Pr.01-11)
When Fcmd > Fmin and Fcmd < Fstart:
If Flow < Fcmd, drive runs directly by Fcmd.
If Flow ≥ Fcmd, drive runs by Fcmd, then rises to Flow according to acceleration time.
The output frequency goes directly to 0 when decelerating to Fmin.
Output Frequency Upper Limit
Default: 599.00
Settings 0.00–599.00 Hz

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD370CP43B-21 and is the answer not in the manual?

Delta VFD370CP43B-21 Specifications

General IconGeneral
BrandDelta
ModelVFD370CP43B-21
CategoryDC Drives
LanguageEnglish

Related product manuals