Chapter 11 Summary of Parameter SettingsC2000 Plus
11-23
Pr. Parameter Name Setting Range Default
03-25
AFM2 Analog Output 2 in REV
Direction
0: Absolute value in output voltage
1: Reverse output 0 V; forward output 0
–10 V
2: Reverse output 5
–0 V; forward output 5–10 V
0
03-27 AFM2 Output Bias -100.00–100.00% 0.00
03-28 AVI Terminal Input Selection
0: 0–10 V
1: 0–20 mA
2: 4–20 mA
0
03-29 ACI Terminal Input Selection
0: 4–20 mA
1: 0–10 V
2: 0–20 mA
0
03-30
PLC Analog Output Terminal
Status
Monitor the status of the PLC analog output terminals
Read
only
03-31 AFM2 Output Selection
0: 0–20 mA output
1: 4–20 mA output
0
03-32 AFM1 DC Output Setting Level 0.00–100.00% 0.00
03-33 AFM2 DC Output Setting Level 0.00–100.00% 0.00
03-35 AFM1 Output Filter Time 0.00–20.00 sec. 0.01
03-36 AFM2 Output Filter Time 0.00–20.00 sec. 0.01
03-44
Multi-Function Output (MO) By
AI Level Source
0: AVI
1: ACI
2: AUI
0
03-45 AI Upper Level (MO) -100.00–100.00% 50.00
03-46 AI Lower Level (MO) -100.00–100.00% 10.00
03-50 Analog Input Curve Selection
0: Normal curve
1: Three-point curve of AVI
2: Three-point curve of ACI
3: Three-point curve of AVI & ACI
4: Three-point curve of AUI
5: Three-point curve of AVI & AUI
6: Three-point curve of ACI & AUI
7: Three-point curve of AVI & ACI & AUI
0
03-51 AVI Lowest Point
Pr.03-28 = 0, 0.00–10.00 V
Pr.03-28 = 1, 0.00–20.00 mA
Pr.03-28 = 2, 4.00–20.00 mA
0.00
0.00
4.00
03-52 AVI Proportional Lowest Point -100.00–100.00% 0.00
03-53 AVI Mid-Point
Pr.03-28 = 0, 0.00–10.00 V
Pr.03-28 = 1, 0.00–20.00 mA
Pr.03-28 = 2, 4.00–20.00 mA
5.00
10.00
12.00
03-54 AVI Proportional Mid-Point -100.00–100.00% 50.00