Chapter 11 Summary of Parameter SettingsC2000 Plus
11-24
Pr. Parameter Name Setting Range Default
03-55 AVI Highest Point
Pr.03-28 = 0, 0.00–10.00 V
Pr.03-28 = 1, 0.00–20.00 mA
Pr.03-28 = 2, 4.00–20.00 mA
10.00
20.00
20.00
03-56 AVI Proportional Highest Point -100.00–100.00% 100.00
03-57 ACI Lowest Point
Pr.03-29 = 0, 4.00–20.00 mA
Pr.03-29 = 1, 0.00–10.00 V
Pr.03-29 = 2, 0.00–20.00 mA
4.00
0.00
0.00
03-58 ACI Proportional Lowest Point -100.00–100.00% 0.00
03-59 ACI Mid-Point
Pr.03-29 = 0, 4.00–20.00 mA
Pr.03-29 = 1, 0.00–10.00 V
Pr.03-29 = 2, 0.00–20.00 mA
12.00
5.00
10.00
03-60 ACI Proportional Mid-Point -100.00–100.00% 50.00
03-61 ACI Highest Point
Pr.03-29 = 0, 4.00–20.00 mA
Pr.03-29 = 1, 0.00–10.00 V
Pr.03-29 = 2, 0.00–20.00 mA
20.00
10.00
20.00
03-62 ACI Proportional Highest Point -100.00–100.00% 100.00
03-63
Positive AUI Voltage Lowest
Point
0.00–10.00 V 0.00
03-64
Positive AUI Voltage
Proportional Lowest Point
-100.00–100.00% 0.00
03-65 Positive AUI Voltage Mid-Point 0.00–10.00 V 5.00
03-66
Positive AUI Voltage
Proportional Mid-Point
-100.00–100.00% 50.00
03-67
Positive AUI Voltage Highest
Point
0.00–10.00 V 10.00
03-68
Positive AUI Voltage
Proportional Highest Point
-100.00–100.00% 100.00
03-69
Negative AUI Voltage Highest
Point
-10.00–0.00 V 0.00
03-70
Negative AUI Voltage
Proportional Highest Point
-100.00–100.00% 0.00
03-71 Negative AUI Voltage Mid-Point -10.00–0.00 V -5.00
03-72
Negative AUI Voltage
Proportional Mid-Point
-100.00–100.00% -50.00
03-73
Negative AUI Voltage Lowest
Point
-10.00–0.00 V -10.00
03-74
Negative AUI Voltage
Proportional Lowest Point
-100.00–100.00% -100.00