Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-02-20
Settings  Functions  Descriptions 
47  Closed brake output 
When drive stops, and the frequency command < Pr.02-34, the 
contact of corresponding multi-function terminal is ON. The contact 
is OFF when the brake delay time exceeds Pr.02-32.   
 
49 
Homing action 
completed 
Activate when homing action is completed.   
50 
Output control for 
CANopen  
Control the multi-function output terminals through CANopen. 
To control RY2, set Pr.02-14 = 50. 
The mapping table of the CANopen DO is shown in the following 
table:  
Physical terminal 
Setting of related 
parameters 
Attribute  Corresponding Index 
RY1  Pr.02-13 = 50  RW  The bit0 at 2026-41 
RY2  Pr.02-14 = 50  RW  The bit1 at 2026-41 
MO1  Pr.02-16 = 50  RW  The bit3 at 2026-41 
MO2  Pr.02-17 = 50  RW  The bit4 at 2026-41 
MO10 
Pr.02-36 = 50  RW 
The bit5 at 2026-41 
RY10  The bit5 at 2026-41 
MO11 
Pr.02-37 = 50  RW 
The bit6 at 2026-41 
RY11  The bit6 at 2026-41 
RY12  Pr.02-38 = 50  RW  The bit7 at 2026-41 
RY13  Pr.02-39 = 50  RW  The bit8 at 2026-41 
RY14  Pr.02-40 = 50  RW  The bit9 at 2026-41 
RY15  Pr.02-41 = 50  RW  The bit10 at 2026-41 
Refer to Section 15-3-5 for more information. 
51 
Analog output control for 
RS-485 interface 
(InnerCOM / Modbus)   
For RS-485 interface (InnerCOM / Modbus) output. 
Physical 
terminal 
Setting of related 
parameters 
Attribute 
Corresponding 
Index 
RY1  Pr.02-13 = 51  RW  bit0 at 2640H 
RY2  Pr.02-14 = 51  RW  bit1 at 2640H   
MO1  Pr.02-16 = 51  RW  bit3 at 2640H   
MO2  Pr.02-17 = 51  RW  bit4 at 2640H   
MO10 or RA10  Pr.02-36 = 51  RW  bit5 at 2640H   
MO11 or RA11  Pr.02-37 = 51  RW  bit6 at 2640H 
RA12  Pr.02-38 = 51  RW  bit7 at 2640H 
RA13  Pr.02-39 = 51  RW  bit8 at 2640H 
RA14  Pr.02-40 = 51  RW  bit9 at 2640H 
RA15  Pr.02-41 = 51  RW  bit10 at 2640H