Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-02-21
Settings  Functions  Descriptions 
52 
Output control for 
communication cards   
Control the output through communication cards (CMC-EIP01, 
CMC-PN01 and CMC-DN01) 
Physical 
terminal 
Setting of 
related 
parameters 
Attribute 
Corresponding 
Address 
RY1  Pr.02-13 = 52  RW  The bit0 of 2640H 
RY2  Pr.02-14 = 52  RW  The bit1 of 2640H 
MO1  Pr.02-16 = 52  RW  The bit3 of 2640H 
MO2  Pr.02-17 = 52  RW  The bit4 of 2640H 
MO10 or RA10  Pr.02-36 = 51  RW  The bit5 of 2640H 
MO11 or RA11  Pr.02-37 = 51  RW  The bit6 of 2640H 
RA12  Pr.02-38 = 51  RW  The bit7 of 2640H 
RA13  Pr.02-39 = 51  RW  The bit8 of 2640H 
RA14  Pr.02-40 = 51  RW  The bit9 of 2640H 
RA15  Pr.02-41= 51  RW  The bit10 of 2640H 
 
65 
Output for both 
CANopen and RS-485 
To control output of CANopen & InnerCOM internal 
communication. 
66  SO output logic A (N.O.) 
Status of the 
drive 
Status of safety output 
Status A (MOx=66)  Status B (MOx=68) 
Normal  Broken circuit (Open)  Short circuit (Close) 
STO  Short circuit (Close)  Broken circuit (Open) 
STL1–STL3  Short circuit (Close)  Broken circuit (Open) 
 
68  SO output logic B (N.C.) 
67 
Analog input level 
reached 
The multi-function output terminals operate when the analog input 
level is between the high level and the low level. 
Pr.03-44: Select one of the analog input channels (AVI, ACI and 
AUI) to be compared. 
Pr.03-45: The high level for the analog input, default is 50%. 
Pr.03-46: The low level for the analog input, default is 10%. 
If analog input > Pr.03-45, the multi-function output terminal 
operates. If analog input < Pr.03-46, the multi-function output 
terminal stops output. 
70 
Fan warning detection 
output 
The terminal works when the internal fan warning activates 
75 
Forward running status 
MO=75 activates (ON) when the drive runs in forward. 
MO=76 activates (ON) when the drive runs in reverse. 
When the drive is in stop status, MO=75 and MO=76 deactivates 
(OFF).