Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-02-22
Settings  Functions  Descriptions 
76 
Reverse running status 
 
  Multi-function output (MO) terminal 
25 
Forward command 
26 
Reverse command 
75 
Forward 
running status 
76 
Reverse 
running status 
Drive runs in 
FWD 
ON OFF ON OFF 
Drive runs in 
REV 
OFF ON OFF ON 
Drive stops 
The drive runs in 
forward and stops. 
The "FWD" light 
on the panel is in a 
steady ON status, 
and MO=25 
remains ON. 
The drive runs in 
reverse and stops. 
The "REV" light on 
the panel is in a 
steady ON status, 
and MO=26 
remains ON. 
OFF OFF 
  When the drive is in stop status, either 
MO=25 or MO=26 activates (ON). 
When the drive is in stop 
status, both MO=75 and 
MO=76 deactivate (OFF). 
 
Example: Crane Application 
   
It is recommended to be used with Dwell function as shown in the following: 
   
  When using the crane application and MOx = 42, Pr.02-34 must be larger than Pr.02-58; Pr.02-
33 must be larger than Pr.02-57.