Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-03-18
 
03-15 
AVI Analog Input Filter Time 
 
03-16 
ACI Analog Input Filter Time 
 
03-17 
AUI Analog Input Filter Time 
 
 
   
 Default: 0.01 
 
 
Settings 0.00–20.00 sec. 
 Analog signals, such as those entering AVI, ACI and AUI, are commonly affected by interference 
that affects the stability of the analog control. Use the Input Noise Filter to create a more stable 
system. 
 When the time constant setting is too large, the control is stable but the control response is slow. 
When the time constant setting is too small, the control response is faster but the control may be 
unstable. For optimal setting, adjust the setting based on the control stability or the control 
response. 
 
03-18 
Analog Input Addition Function 
 
 
   
 Default: 0 
 
 
Settings  0: Disabled (AVI, ACI, AUI) 
1: Enabled 
 When Pr.03-18 = 1: 
Example 1: Pr.03-00 = Pr.03-01=1, Frequency command= AVI+ACI 
Example 2: Pr.03-00 = Pr.03-01 = Pr.03-02 = 1, Frequency command = AVI+ACI+AUI 
Example 3: Pr.03-00 = Pr.03-02=1, Frequency command = AVI+AUI 
Example 4: Pr.03-01 = Pr.03-02=1, Frequency command = ACI+AUI   
 When Pr.03-18=0 and the analog input selection settings (Pr.03-00, Pr.03-01 and Pr.03-02) are 
the same, AVI has priority over ACI and AUI (AVI > ACI > AUI).   
 
 
03-19 
Signal Loss Selection for the Analog Input 4–20 mA 
 
 
   
 Default: 0 
 
 
Settings 0: Disabled 
1: Continue operation at the last frequency 
2: Decelerate to 0 Hz 
3: Stop immediately and display ACE 
4: Operate with output frequency lower limit (Pr.01-11) and displays ANL 
 Determines the treatment when the 4–20 mA signal is lost [AVIc (Pr.03-28 = 2) or ACIc (Pr.03-29 
= 0)].   
 When Pr.03-28 ≠ 2, the voltage input to AVI terminal is 0–10 V or 0–20 mA, and Pr.03-19 is invalid.