Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-03-19
 When Pr.03-29 ≠ 0, the voltage input to ACI terminal is 0–10 V or 0–20 mA, and the Pr.03-19 is 
invalid. 
 When the setting is 1,2, or 4, the keypad displays the warning code “ANL”. It keeps blinking until 
the ACI signal is recovered. 
 When the drive stops, the condition that causes the warning does not exist, so the warning 
automatically disappears. 
 The ACI (4–20 mA) signal loss level is 3.6 mA, and the return level is 4 mA. 
 
03-20 
AFM1 Multi-Function Output 1 
 
03-23 
AFM2 Multi-Function Output 2 
 
 
   
 Default: 0 
 
 
Settings 
0
–25 
Function Chart 
Settings  Functions  Descriptions 
0  Output frequency (Hz)  Maximum frequency Pr.01-00 is processed as 100%. 
1  Frequency command (Hz)  Maximum frequency Pr.01-00 is processed as 100%. 
2  Motor speed (Hz)  Maximum frequency Pr.01-00 is processed as 100%. 
3  Output current (rms)  (2.5 × drive rated current) is processed as 100% 
4  Output voltage  (2 × motor rated voltage) is processed as 100% 
5  DC bus Voltage  450 V (900 V)=100% 
6 Power factor 
-1.000
–1.000=100% 
7  Power  (2 × drive rated power) is processed as 100% 
8  Output torque  Full-load torque = 100% 
9 AVI 
0
–10 V = 0–100% 
10 ACI 
4
–20 mA = 0–100% 
11 AUI 
-10
–10 V = 0–100% 
12  Iq current command  (2.5 × drive rated current) is processed as 100% 
13  Iq feedback value  (2.5 × drive rated current) is processed as 100% 
14  Id current command  (2.5 × drive rated current) is processed as 100% 
15  Id feedback value  (2.5 × drive rated current) is processed as 100% 
18  Torque command  Motor rated torque = 100% 
19  PG2 frequency command 
Maximum operation frequency (Pr.01-00) is processed as 
100%. 
20  CANopen analog output 
For CANopen communication analog output 
Terminal Address 
AFM1 2026-A1 
AFM2 2026-A2 
AO10 2026-AB 
AO11 2026-AC