Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-07-13
D.  Time for steady-state output frequency is larger than Pr.07-42 (Delay Time for AES) 
E.  Output current is smaller than or equal to 90% of the drive’s rated current 
  The prerequisites for invalid power factor energy-saving improvement (Pr.07-21=1) are: 
1.  A changing output frequency 
2.  Output current is larger than 90% of the drive’s rated current 
 
 Automatic energy-saving optimization (Pr.07-21=2): 
  Controls the output voltage to minimize the motor’s losses for optimal energy-saving. The 
motor’s losses are calculated by motor parameter auto-tuning and energy-saving coefficient. 
  Automatic energy-saving optimization control is according to the block diagram below: 
 
  The prerequisites for valid automatic energy-saving optimization (Pr.07-21=2) are: 
A.  Output frequency is larger than Pr.07-41 (Minimum Frequency for AES) 
B.  The drive is in a steady-state output frequency status 
C.  Time for steady-state output frequency is larger than Pr.07-42 (Delay Time for AES)