Chapter 12 Descriptions of Parameter SettingsC2000 Plus 
 
12.1-07-12
 
 
07-21 
Automatic Energy-Saving Selection 
 
 
   
 Default: 0 
 
 
Settings 0: Disabled 
1: Power factor energy-saving improvement (for VF, SVC and VFPG control 
modes) 
2: Automatic energy-saving (AES) optimization (for VF, SVC and VFPG 
control modes) 
  Different control modes for Pr.07-21:
Motor  Induction Motor (IM) 
Permanent Magnet   
Synchronous Motor (PM) 
Synchronous 
Reluctance 
Motor (SynRM) 
Control Mode  VF  VFPG SVC FOCPG FOC 
PM 
SVC 
FOCPG 
PM 
PM 
FOC 
HFI 
1: Power factor 
energy-saving 
improvement 
✓  ✓  ✓ 
         
2: Automatic 
energy-saving 
optimization 
✓  ✓  ✓ 
         
 Power factor energy-saving improvement (Pr.07-21=1): 
  When the automatic energy-saving function is enabled, the drive runs with full-voltage during 
acceleration and deceleration, and runs with the optimal voltage that is automatically 
calculated by the load power during constant operation. It is not recommended to use this 
function for applications that require frequent load changes or when the load is close to full-
load during operation. 
  The prerequisites for valid power factor energy-saving improvement (Pr.07-21=1) are: 
A.  Power factor angle is larger than Pr.07-43 (Targeted Power Factor Angle for AES) 
B.  Output frequency is larger than Pr.07-41 (Minimum Frequency for AES) 
C.  The drive is in a steady-state output frequency status