Chapter 12 Description of Parameter SettingsCP2000   
 
12.1-00-10 
 
 
Operation Command (AUTO) Source 
  
 
  Default: 0 
  Settings  0: Digital keypad 
    1: External terminals   
    2: RS-485 communication 
    3: CANopen communication card 
    5: Communication card (does not include CANopen card) 
 Determines the operation frequency source in AUTO mode. 
 When you control the operation command by the keypad KPC-CC01, keys RUN, STOP and JOG 
(F1) are valid. 
 
 
Stop Method 
  
 
  Default: 0 
  Settings  0: Ramp to stop 
    1: Coast to stop 
 Determines how the motor is stopped when the drive receives the Stop command.   
 
  Ramp to stop: the AC motor drive decelerates to 0 or the minimum output frequency according 
to the set deceleration time, and then to stop (according to Pr.01-07).     
  Coast  to  stop: the  AC  motor  drive  stops  output  immediately,  and  the  motor  coasts  to  stop 
according to the load inertia. 
(1) Use “ramp to stop” for the safety of personnel, or to prevent material from being wasted in   
      applications where the motor must stop immediately after the drive stops. You must set the   
      deceleration time accordingly.   
(2) If idling is allowed, or the load inertia is large, use “coast to stop”. For example, blowers,   
      punching machines and pumps 
 
 
Control of Motor Direction 
  
 
  Default: 0 
  Settings  0: Enable forward / reverse   
    1: Disable reverse   
    2: Disable forward 
  Enables the AC motor drives to run in the forward and reverse direction. You can use it to prevent 
a motor from running in a direction that would cause injure or damage to the equipment.