Chapter 12 Description of Parameter SettingsCP2000   
 
 
12.1-08-1 
08 High-function PID Parameters 
 This parameter can be set during operation.     
 
 
Terminal Selection of PID Feedback 
 
 
  Default: 0 
  Settings  0: No function 
    1: Negative PID feedback: by analog input (Pr.03-00–03-02) 
    4: Positive PID feedback: by analog input (Pr.03-00–03-02) 
  Pr.08-00≠0 enables the PID function. 
  Negative feedback means:   
+target value – feedback. The detection value increases by increasing the output frequency. 
  Positive feedback means:   
-target value + feedback. The detection value decreases by increasing the output frequency. 
  When  Pr.08-00≠7  neither  ≠8,  the  input  value  is  disabled.  The  value  of  the  setting  does  not 
remain the same after the drive is OFF. 
  Related applicable parameters: Pr.00-20, Pr.03-00–03-02 
When enable  the  PID function (Pr.08-00 ≠  0), if Pr.00-20  is set to  2  “External analog  input”, 
Pr.03-00–03-02 need to be set to 4 “PID target value” accordingly.   
 
 
 
Master Frequency Command (AUTO) Source / Source Selection of the PID Target 
  
 
  Default: 0 
  Settings  0: Digital keypad 
    1: RS-485 serial communication 
    2: External analog input (Refer to Pr.03-00) 
    3: External UP/DOWN terminal 
    6: CANopen communication card 
    8: Communication card (does not include CANopen card)