Chapter 3. Machine Adjustment Procedure | VFD-VJ 
 
3-20
Slave setting 
  Pr.01-01=1 
Source of operation command 
Setting value   
of Pr. 01-01 
0: Operation by using the digital keypad 
1: Operation by using the external terminals. The Stop button on the 
keypad is disabled. 
2: Communication using RS-485. The Stop button on the keypad is 
disabled 
  Set Pr.01-01=2 
Source of operation command 
Setting value   
of Pr.01-01 
0: Operation by using the digital keypad 
1: Operation by using the external terminals. The Stop button on the 
keypad is disabled. 
2: Communication using RS-485. The Stop button on the keypad is 
disabled 
  Set Pr.03-15 = 1 
Source of Frequency Command 
Setting value   
of Pr. 03-15 
0: Digital Operation Panel 
1: RS485 Communication 
2~5: reserved 
6: CANopen   
  Shut down the power and then supply the power again 
Set an arbitrary value of the frequency command at the Master to check if the Slave has the 
same value of the frequency command 
Set 10rpm at the Master and then press RUN to see if the Slave is also running. If not, check 
the wiring or the parameter setting for any problem 
  Set Slave Pr.03-13 = 2 
Confluence Master/Slave Selection 
Setting value   
of Pr.03-13 
0: No function 
1: Master 1 
2: Slave/Master 2 
3: Slave/Master 3 
  Pr.03-21 can be set at the Slave to decide if the Salve is performing the reversed operation for 
depressurization. 
NOTE: If it is required to reverse the operation for depressurization at the Slave, it is necessary 
to make sure that the pump outlet port is not installed with a check valve and Pr.03-16 should 
be set as 500%