Chapter 14 Fault CodesMS300
590
ID
Display on LCD Keypad
Fault Name
Fault Descriptions
54
Illegal command
(CE1)
Communication command is illegal
Action and Reset
Action Condition
When the function code is not 03, 06, 10, or 63.
Action Time
Immediately act
Fault Treatment Parameter
N/A
Reset Method
Manual reset
Reset Condition
Immediately reset
Record
No
Cause
Corrective Actions
Incorrect communication
command from the upper unit
Check if the communication command is correct.
Malfunction caused by
interference
Verify the wiring and grounding of the communication circuit. It is recommended
to separate the communication circuit from the main circuit, or wire in 90 degree
for effective anti-interference performance.
Different communication setting
from the upper unit
Check if the setting for Pr.09-04 is the same as the setting for the upper unit.
Disconnection or bad connection
of the cable
Check the cable and replace it if necessary.

Table of Contents

Other manuals for Delta VFD4A8MS21ANSAA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD4A8MS21ANSAA and is the answer not in the manual?

Delta VFD4A8MS21ANSAA Specifications

General IconGeneral
BrandDelta
ModelVFD4A8MS21ANSAA
CategoryDC Drives
LanguageEnglish

Related product manuals