3. Machine Adjustment Procedure
3-9
Set the Parameter 01-17
The rated current of the synchronous motor
Setting value
of Parameter
01-17
0~655.35 Amps
Set the Parameter 01-18
The rated power of the synchronous motor
Setting value
of Parameter
01-18
0.00 – 655.35kW
Set the Parameter 01-19
The rated speed (rpm) of the synchronous motor
Setting value
of Parameter
01-19
0~65535
Set the Parameter 01-20
Number of poles of the synchronous motor
Setting value
of Parameter
01-20
2~20
Set the Parameter 01-21
The inertia of the synchronous motor’s rotor
Setting value
of Parameter
01-21
0.0~6553.5 *10
-4
kg.m
2
Check if the motor can be separated from the pump
If it can be separated, set the Parameter 01-07 as 5 and carry out the parameter measurement
of the synchronous motor
If it cannot be separated, open the safety valve, set the Parameter 01-07 as 5 and carry out
the parameter measurement of the synchronous motor
Motor Parameter Auto Tuning
Setting value
of Parameter
01-07
0: No function
1: Rolling test for induction motor(IM) (Rs, Rr, Lm, Lx, no-load current)
2: Static test for induction motor(IM)
3: Reserved
4: Auto measure the angle between magnetic pole and PG origin
5: Rolling test for PM motor
During the automatic measurement process of the synchronous motor, the digital keypad will
show the message “tun”. After the measurement is finished, the motor automatically shuts
down, and the measurement values are stored into Parameters 01-22 to 01-25.If the digital