Chapter 12 Description of Parameter SettingsC2000-HS
12.2-00-18
Parameter Description Default
Pr.11-00 System control 0
Pr.11-01 Per unit of system inertia 256
Pr.11-02
ASR1/ASR2 switch frequency
(it is suggested to set the switch frequency higher than
Pr.10-39)
7Hz
Pr.11-03 ASR1 low-speed bandwidth 10Hz
Pr.11-04 ASR2 high-speed bandwidth 10Hz
Pr.11-05 ASR zero-speed bandwidth 10Hz
PM FOC+PG With-load starting adjustment procedure
With-load Operation Adjustment:
C1. Low-frequency load performance, when the drive operates under ASR1/ASR2 switch
frequency (Pr.11-02):
a. If the low-speed frequency cannot start-up with load or the rotor speed is not smooth,
increase Pr.11-03 (ASR1 low-speed bandwidth), or increase Pr.11-01 (Per-unit system
inertia).
b. If an oscillation or over current (oc) error occurs at low-speed frequency, decrease
Pr.11-03 (ASR1 low-speed bandwidth) or decrease Pr.11-01 (Per-unit system inertia).