Chapter 12 Description of Parameter SettingsC2000-HS 
 
12.2-00-36 
  Basic Motor Parameters Adjustment 
1.  Parameter reset 
Reset Pr.00-02=10 to the default value. 
2.  Select PM motor type 
Pr.05-33 = 1 or 2 (SPM or IPM) 
3.  Motor nameplate parameter setting 
Parameter  Description 
Pr.01-01  Output frequency of motor 1 (Hz) 
Pr.01-02  Output voltage of motor 1 (V
AC
) 
Pr.05-34  Full-load current for PM (A) 
Pr.05-35  Rated power for PM (kW) 
Pr.05-36  Rated speed for PM (rpm) 
Pr.05-37  Pole number for PM (poles) 
Pr.05-38  System inertia for PM (kg-cm
2
) 
4.  Motor parameter auto-tuning: 
Set Pr.05-00=5 (rolling auto-tuning for PM) or 13 (static auto-tuning for PM), press RUN to 
finish the motor parameter auto-tuning, then you will get the following parameters: 
Parameter  Description 
Pr.05-39 
Stator resistance for a permanent magnet motor (Ω) 
Pr.05-40  Permanent magnet motor Ld (mH) 
Pr.05-41  Permanent magnet motor Lq (mH) 
Pr.05-43 
Ke parameter of a permanent magnet motor (V
phase
,
rms 
/ krpm) 
(When Pr.05-00=5, the Ke parameter is measured based on the actual 
motor rotation.) 
(When Pr.05-00=13, the Ke parameter is automatically calculated based 
on the motor power, current and rotor speed.) 
If an auto-tuning error (AUE) occurs, refer to Section 14 “Fault Codes and Descriptions” for 
further treatment. 
AUE Error (code)  Description 
AUE (40)  Auto-tuning error 
AUE1 (142)  Auto-tuning error 1 (No feedback current error) 
AUE2 (143)  Auto-tuning error 2 (Motor phase loss error) 
5.  Control mode setting 
Pr.00-10=0, speed mode 
Pr.00-11=6, PM Sensorless control mode 
6.  After motor auto-tuning, cycle the power. 
7.  Measure the initial magnetic pole angle of PM 
Set Pr.10-53 PM initial rotor position detection method 
0: Disable 
1: Internal 1/4 rated current attracting the rotor to zero degrees 
2: High frequency injection 
3: Pulse injection 
(Set to 2 for IPM; set to 3 for SPM. If these settings cause problems, then set the parameter to 
1.)