Chapter 14 Fault Codes and DescriptionsC2000-HS 
 
14-7 
ID*  Display on LCM Keypad  Fault Name  Fault Descriptions 
8 
 
Over-voltage during 
deceleration   
(ovd) 
DC BUS over-voltage during deceleration. 
When  ovd  occurs,  the  drive  closes  the  gate  of  the 
output  immediately,  the  motor  runs  freely,  and  the 
display shows an ovd error.   
Action and Reset 
Action level  820V
DC
 
Action time  Immediately act when DC BUS voltage is higher than the level 
Fault treatment parameter  N/A 
Reset method  Manual reset 
Reset condition  Reset only when DC BUS voltage is lower than 90% of the over-voltage level 
Record  Yes 
Cause  Corrective Actions 
Deceleration time is too short, 
causing too large regenerative 
energy of the load 
1.  Increase the setting value of Pr. 01-13, Pr. 01-15, Pr. 01-17 and Pr. 01-19 
(deceleration time) 
2.  Connect brake resistor, brake unit or DC BUS on the drive. 
3.  Reduce the brake frequency. 
4.  Replace the drive with a larger capacity model. 
5.  Use S-curve acceleration/deceleration. 
6.  Use over-voltage stall prevention (Pr. 06-01). 
7.  Use auto-acceleration and auto-deceleration (Pr. 01-44). 
8.  Adjust braking level (Pr. 07-01 or the bolt position of the brake unit). 
The setting for stall prevention 
level is smaller than no-load 
current 
The setting for stall prevention level should be larger than no-load current 
Power voltage is too high 
Check if the input voltage is within the rated AC motor drive input voltage range, 
and check for possible voltage spikes. 
ON/OFF switch action of phase-in 
capacitor in the same power 
system 
If  the  phase-in capacitor or active  power  supply  unit acts in  the  same power 
system, the input voltage may surge abnormally in a short time. In this case, 
install an AC reactor. 
Motor ground fault 
The ground short circuit current charges the capacitor in the main circuit through 
the power. Check if there is ground fault on the motor cable, wiring box and its 
internal terminals. 
Troubleshoot the ground fault. 
Incorrect wiring of brake resistor or 
brake unit 
Check the wiring of brake resistor or brake unit. 
Malfunction caused by interference 
Verify the wiring of the control circuit and wiring/grounding of the main circuit to 
prevent interference.