Chapter 16 PLC Function ApplicationsC2000-HS 
 
16-120
 
Pr. 01-12: Acceleration time 1 
Pr. 01-13: Deceleration time 1 
Pr. 01-14: Acceleration time 2 
Pr. 01-15: Deceleration time 2 
Pr. 01-16: Acceleration time 3 
Pr. 01-17: Deceleration time 3 
Pr. 01-18: Acceleration time 4 
Pr. 01-19: Deceleration time 4 
Pr. 02-12: Select MI Conversion Time mode:   
Pr. 02-18: Select MO Conversion Time mode:   
Pr. 04-50–Pr. 04-69: PLC register parameter 0 - 19 
Pr. 08-04: Upper limit of integral 
Pr. 08-05: PID output upper limit   
Pr. 10-17: Electronic gear A   
Pr. 10-18: Electronic gear B 
Pr. 11-34: Torque command 
Pr. 11-43: P2P highest frequency   
Pr. 11-44: Position control acceleration time   
Pr. 11-45: Position control deceleration time 
Calculation of the number of times written is based on whether the written value is 
modified. For instance, writing the same value 100 times at the same time counts 
as writing only once.   
When  writing  a  PLC  program,  if  unsure  of  usage  of  the  WPR  command,  we 
recommend that you use the WPRP command.