  Situation 3: Unexpected power shut down or power loss 
Pr.07-13 = 1 and power does not recover 
The keypad displays the “dEb” warning and the drive stops after decelerating to the lowest 
operating frequency. When the DC bus voltage is lower than the Lv level, the drive 
disconnects the soft start relay until the power completely runs out. 
 
  Situation 4: Unexpected power shut down or power loss   
Pr.07-13 = 2 and power does not recover 
The drive decelerates to 0 Hz. The DC bus voltage continues to decrease until the voltage 
is lower than the Lv level, and then the drive disconnects the soft start relay. The keypad 
displays “dEb” warning until the drive completely runs out of power. 
  Situation 5: Pr.07-13 = 2 and power recovers after the DC bus voltage is lower than the Lv 
level. 
The drive decelerates to 0 Hz. The DC bus voltage continues to decrease until the voltage 
is lower than the Lv level, and then the drive disconnects the soft start relay. The soft start 
relay closes again after the power recovers and the DC bus voltage is higher than the Lv 
return level. When the DC bus voltage is higher than the dEb return level, the drive 
maintains the frequency for three seconds and starts to accelerate linearly. The “dEb” 
warning on the keypad is automatically cleared.