CAIRplus Installation
PR-2009-0096-GB • Subject to modifications • R8-10/2015 43
For units with outside-air or mixed-air operation consider the following:
6.3.2 Installing evaporator/condenser components
Use special tools and fittings for handling service connections.
9 The units are charged with protective nitrogen that audibly discharges when caps
are removed.
6.3.3 Installing coils with a liquid-coupled energy recovery system
Refer to "Installing air-handling components for cooling/heating applications" on
page 42.
ATTENTION
Risk of damage to the unit!
Protect the heat exchanger in unit from ice and freezing at ambient
temperatures below the freezing point.
Use proper antifreeze agents in the water circuit.
Notice!
Using glycol is allowed, but the glycol concentration shall not exceed 50% of
the total charge.
A higher quantity can cause operating faults.
ATTENTION
Risk of environmental damage!
Properly dispose of all liquids (refrigerants) in an environmentally-friendly way
in accordance with the locally applicable laws and regulations.