CAIRplus Commissioning and Maintenance
PR-2009-0096-GB • Subject to modifications • R8-10/2015 79
8.13 Humidifier assembly
For steam humidifiers:
Depending on the type of humidifier and installation location, you have to check differ-
ent criteria, such as:
Quality of Water
Microbial count
Drain cycles
Deposit build-up, etc.
Refer to the corresponding instructions specified in the supplied documentation.
8.14 Damper blades and shut-off dampers
8.14.1 Commissioning of dampers and shut-off dampers
DANGER!
Please consider the safety instructions on page 5 and page 55ff when performing
all the described activities!
Complete the following commissioning steps:
If several dampers are linked together, ensure that the connecting linkage is
installed properly and is moving freely.
Check all screw connections for proper fit.
For actuators
Adjust the connecting linkage to ensure a turning angle of 90° with damper blades
reaching their final position when closed (consider tightening torques).
Check if the damper actuator moves to its final positions.
Ensure proper operation of this component.
Do not start up the fans with closed dampers.
Electrical hazard and danger of rotating unit parts with sharp edges!
OBSERVE PERSONAL PROTECTION MEASURES
Please consider the safety instructions on page 5 and page 55ff when
performing all the described activities!
Danger of injury from scalding!
Hot steam escapes if an air vent is open!
Consider scalding hazard.
Slowly open air vents.
For all jobs wear the appropriate personal protective equipment.
HAZARDOUS VOLTAGE AND RISK OF ROTATING COMPONENTS!
OBSERVE PERSONAL PROTECTION MEASURES
Please consider the safety instructions on page 5 and page 55ff when
performing all the described activities!